CU 6002 4P Cca

Data cable, U/FTP, Category 6, AWG23, Euroclass Cca
300 MHz

1 Inner conductor: AWG23 Bare copper wire
2 PE insulated conductor: 1.3 mm Ø
3 Screen (pair): Alu PETP foil
4 Drain wire: Tinned copper wire
5 Outer sheath: FRNC/LS0H orange RAL 2003

01_RoHS 04_Propagation 05_Spread- 02_PoE 10_Schielded_EN 06_Density 08_System- 03_LS0H CPR_Cca CPR_Dca CPR_Eca CPR_Fca_sw

Product variants & stock

Article No. Stock ProductReaction to fireDimensions n x p x [mm (AWG)]Outer sheath dimensions [mm]CU rate [kg/km]Weight [kg/km]Fire load [kWh/m]Packing unitGTIN / EAN
18293600CK
CU 6002 4PCca-s1a,d1,a14 x 2 x 0.55 (AWG23)6.820.0480.151000 m drum40393910040227
18293600CL
CU 6002 4PCca-s1a,d1,a14 x 2 x 0.55 (AWG23)6.820.0480.15500 m drum40393910040210

Technical specifications

Electrically and mechanically advanced quality Cat.6 data cable - fulfils the requirements of ISO/IEC 11801, IEC 61156-5, EN 50173-1 and EN 50288-5-1. Good shielding effect due to individually screened pairs. Compatible with all current connecting hardware in accordance with EN 50173 and ISO/IEC 11801.
AWG 23
Tensile strength (4P) 95 N
Minimum bending radius during installation 56 mm
Minimum bending radius permanently installed 28 mm
Minimal crush resistance / 10cm 1000 N
Minimum number of impacts 10
Solid / Flex Solid wire
Segregation class c
Category Cat.6
Loop resistance at 20 °C 150 Ω/km
Operating capacity 42 pF/m
Delay skew 5 ns/100 m
Impedance at 100 MHz, ±5Ω 100 Ω
Transfer impedance 1/10/30 MHz < 50/100/200 mΩ/m
Near end unbalance attenuation LCL at 1-600 MHz 40 dB
NVP % 79
Coupling attenuation 55 dB
GBit/s Up to 1 Gbit/s
Shielding shielded
Data cable for structured premises cabling.
For the transmission of digital and analogue voice, video and data signals.
Suitable for all ICT network applications up to class E applications (250 MHz) in accordance with EN 50173-1 and ISO/IEC 11801.
Applicable for Power over Ethernet (PoE) / PoE+.
Wire colour white/blue, white/orange, white/green, white/brown, according to IEC 60189 and IEC 60708
Field of application Indoor
Installation temperature 0 °C - +50 °C
Operating temperature -20 °C - +60 °C
Imprint DATWYLER «cable type» «additional text» «batch number» «meter marks»
Reaction to fire EN 13501-6
Euroclass Cca
Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA
Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1
Cables standard ISO/IEC 61156-5, EN 50288-5-1
Cat./Class Cat.6 / Class E
PoE IEEE 802.3bt Type 4 (100W)
Outer sheath material FRNC/LSZH
Outer sheath colour orange

Documentation