J-H(St)H...Bd fire alarm

火灾警报线缆,最大. 300V
无卤素, 防火性能卓越
VDE 0815

3 隔离材料: 塑胶带
5 屏蔽层: 覆塑铝箔
6 外护套: FRNC/LS0H
2 绝缘材料: 无卤聚合复合导线
4 接地线: 镀锡铜丝
1 导体: 实芯线

07_Circuit- 04_Propagation 05_Spread 06_Density 08_System- 03_LS0H

产品型号和库存

产品编号 库存 产品外护套颜色芯数外护套 直径 [mm]CU 率 [kg/km]重量 [kg/km]火灾负载 [kWh/m]包装单位GTIN / EAN
157892
J-H(St)H...Bd fire alarm 2x2x0.8 mm红色26.525590.16by the metre40393910207637
157893
J-H(St)H...Bd fire alarm 4x2x0.8 mm红色28.5451110.29by the metre40393910207620
157894
J-H(St)H...Bd fire alarm 6x2x0.8 mm红色210.5651320.35by the metre40393910207613
157895
J-H(St)H...Bd fire alarm 10x2x0.8 mm红色2131062160.55by the metre40393910207606
1172017
J-H(St)H...Bd fire alarm 20x2x0.8 mm红色215.52065081.21by the metre40393910107104
1172018
J-H(St)H...Bd fire alarm 30x2x0.8 mm红色216.33075991.36by the metre40393910107098
1172019
J-H(St)H...Bd fire alarm 40x2x0.8 mm红色216.54077871.67by the metre40393910107081
1172021
J-H(St)H...Bd fire alarm 80x2x0.8 mm红色231.580914763.18by the metre40393910107074
1172022
J-H(St)H...Bd fire alarm 100x2x0.8 mm红色238101018054.07by the metre40393910107067

技术规格书

适用于对阻燃性能要求较高的、人流量较大及经济繁荣区域的静电屏蔽线缆;可传输ICT以太网系统的无损数据及信号;不论是在干燥环境下或是潮湿环境下,在墙体内部或外部都可以安装
可实现户外安装;不可用于地下安装,不能传输高压
导体允许的最大操作温度可达到+70°C
操作能力 120
测试电压 50Hz, 芯/芯 800
峰值电压 300
电容耦合0,8 mm, 100m @ 800Hz 200
电容耦合 0,6 mm, 100m @ 800Hz 300
最大回路电阻 0,8 mm 73.2
最大线圈阻抗 0,6 mm 130
最小绝缘阻抗 100
测试电压 50Hz, 芯/屏蔽 800
绝缘完整性 No
电路完整性 No
安装温度 -5 °C - +50 °C
操作温度 -30 °C - +70 °C
最小弯曲,安装时 (多芯) 7.5 x D
最小永久 弯曲半径(多芯) 2.5 x D
注意 其余的尺寸信息可根据需求定制
导体 裸铜丝实心, 0.6 or 0.8 mm直径
绝缘材料 无卤高分子化合物, EN 50290-2-26
芯线颜色 VDE 0815
屏蔽层 带排扰线的铝层压塑料箔,铜镀锡
外护套 无卤高分子化合物, EN 50290-2-27
绞合 核心扭曲成星形四边形,四边形扭曲成单位
烟密度 EN 61034-1/-2, IEC 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Section 4.3.3 SD
零卤素无腐蚀性气体 EN 60754-1/-2, IEC 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Section 4.3.3 SA
火焰传播 EN 60332-1-2, IEC 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Section 4.3.3 F1
火焰蔓延 EN 60332-3-24, IEC 60332-3-24, AREI-RGIE Section 4.3.3 F2