CU 7725 4P / 2x4P F8

Data cable, S/FTP, 25GBase-T, AWG22, Euroclass Dca
1300 MHz

1 Inner conductor: AWG22 Bare copper wire
2 PE insulated conductor: 1.5 mm ∅;
3 Screen (pair): Alu PETP foil
4 Overall screen: Tinned braided copper
5 Outer sheath: FRNC/LS0H

01_RoHS 04_Propagation 05_Spread 09_Oil- 02_PoEp_gn 10_Schielded_EN 06_Density 08_System- 03_LS0H CPR_Dca CPR_Eca

Varianti di prodotto e stock

Articolo n. Stock ProdottoReaction to fireDimensions n x p x [mm (AWG)]Dimensioni della guaina esterna [mm]Tasso di CU [kg/km]Weight [kg/km]Fire load [kWh/m]Unità di imballaggioGTIN / EAN
19434900DK
CU 7725 4PDca-s2,d1,a14 x 2 x 0.62 (AWG22)7.634.9620.181000 m tamburo40393910022872
19435000DL
CU 7725 2x4PDca-s2,d1,a12 x (4 x 2 x 0.62 (AWG22))7.6 x 16.269.81250.36500 m tamburo40393910022841

Specifiche tecniche

Electrically and mechanically superior quality Cat.7A data cable with extended frequency range up to 1300 MHz - exceeds the requirements of ISO/IEC 11801, IEC 61156-5, IEC 61156-7, EN 50173-1 and EN 50288-9-1. Excellent shielding effect due to individually screened pairs and overall copper braid. Easy identification of wires thanks to longitudinal colour markings. Compatible with all current connecting hardware in accordance with EN 50173 and ISO/IEC 11801.
AWG 22
Resistenza alla trazione (4P) 120 N
Resistenza alla trazione (2x4P) 240 N
Curvatura minima durante l'installazione 64 mm
Minimum bending radius permanently installed 32 mm
Resistenza minima allo schiacciamento / 10cm 1000 N
Minimum number of impacts 10
Solid / Flex stabile
Segregation class d
Categoria Cat.7A
Loop resistance at 20 °C 116 Ω/km
Operating capacity 43 pF/m
Ritardo Skew 15 ns/100 m
Impedenza a 100 MHz, ±5Ω 100 Ω
Transfer impedance 1/10/30 MHz < 5/5/8 mΩ/m
Near end unbalance attenuation LCL at 1-600 MHz 40 dB
NVP % 76
Attenuazione di accoppiamento 85 dB
GBit/s A 25 Gbit/s (lunghezza massima 50 m)
Schermatura schermati
High-end data cable for data centres and for structured premises cabling.
For the transmission of digital and analogue voice, video and data signals.
Suitable for all ICT network applications up to 25GBase-T (1250 MHz) up to 50 m (Channel) and up to class FA (1000 MHz) up to 100 m in accordance with EN 50173-1 and ISO/IEC 11801 as well as for multimedia applications in the CATV frequency range up to 862 MHz in accordance with IEC 15018.
Due to the increased wire section eminently suited for Power over Ethernet (PoE), PoE+ and 4PPoE.
Colore del filo bianco/blu-bianco, bianco/arancio-bianco, bianco/verde-bianco, bianco/marrone-bianco (con strisce longitudinali)
Campo di applicazione Interno
Installation temperature 0 °C - +50 °C
Operating temperature -20 °C - +60 °C
Impronta DATWYLER «cable type» «additional text» «batch number» «meter marks»
Reaction to fire EN 13501-6
Euroclass Dca
Densità del fumo IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
Zero alogeni nessun gas corrosivo IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA
Propagazione della fiamma AREI-RGIE Art.104-F1, EN 60332-1-2, IEC 60332-1-2, VDE 0482-332-1-2
Flame spread IEC 60332-3-24, EN 60332-3-24, AREI-RGIE Art.104-F2
Standard dei cavi ISO/IEC 61156-5, EN 50288-9-1
Cat./Class Cat.7A / Class FA
PoE IEEE 802.3bt Type 4 (100W)
Materiale della guaina esterna FRNC/LSZH
Colore della guaina esterna arancia

Documentazione