Tornare a: Cavi in rame 










CU 8203 4P
1 Inner conductor: AWG23 Bare copper wire
2 PE insulated conductor: 1.6 mm ∅;
3 Screen (pair): Alu PETP foil
4 Overall screen: Tinned braided copper
5 Outer sheath: FRNC/LSOH Orange RAL 2003












Descrizione
Electrically and mechanically superior quality Cat.8.2 data cable – exceeds the requirements of ISO/IEC 11801, IEC 61156-5, EN 50173-1, EN 50288-12-1 and IEC 61156-9.
Excellent shielding effect due to individually screened pairs and overall copper braid.
Compact cable design.
Compatible with all current connecting hardware in accordance with EN 50173 and ISO/IEC 11801.
- High-end data cable for data centres.
Developed particularly for 40 GBase-T transmission with maximum channel length of 30 metres in End of Row or Top of Rack (EoR / ToR) applications in data centres.
For the transmission of digital and analogue voice, video and data signals.
Suitable for all ICT network applications up to 2000 MHz.
Applicable for Power over Ethernet (PoE / PoE+).
- Reaction to fire (Euroclasses) EN 13501-6: Cca
- Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2
- Flame Propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2
- Flame Spread IEC 60332-3-24, EN 60332-3-24
- Smoke Density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2
- Cat./Class Cat.8.2 / Class I/II
- PoE IEEE 802.3bt Type 4 (100W)
- Category Cat.8.2
- Attenuazione di accoppiamento 75 dB
- Ritardo Skew 10 ns/100 m
- Schermatura shielded
- GBit\s Up to 40 Gbit/s
- Impedenza a 100 MHz, ±5Ω 100 Ω
- Loop resistance at 20°C 135 Ω/km
- Near end unbalance attenuation LCL at 1-600 MHz 20 dB
- NVP % 75
- operating capacity 44 pF/m
- Transfer impedance 1/10/30 MHz
8/10/40 mΩ/m
- Installation temperature 0 °C - +50 °C
- Operating temperature -20 °C - +60 °C
- Campo di applicazione Interno
- Impronta DATWYLER «cable type» «additional text» «batch number» «meter marks»
- Colore del filo bianco - blu/blu, bianco arancio/arancione, bianco verde/verde, bianco marrone/marrone in accordo con IEC 60189 e IEC 60708 (contrassegnato da un anello)
- AWG 23
- Curvatura minima durante l'installazione 64 mm
- Minimum bending radius permanently installed 32 mm
- Resistenza minima allo schiacciamento / 10cm 1000 N
- Minimum number of impacts 3
- Solid / Flex stabile
- Resistenza alla trazione (4P) 110 N
Documentazione
Versioni
Article No. | Magazzino | Prodotto | Numero di coppie | AWG | Fire load (MJ/m) | Reaction To Fire | Dimensions n x p x [mm (AWG)] | Outer sheath colour | Numero di core | Diametro mm | Outer sheath material | Diametro esterno della guaina [mm] | Tasso di CU [kg/km] | Weight [kg/km] | Fire load [kWh/m] | Number of cables | Packing unit |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
19200900CK | CU 8203 4P | 4 | AWG23 | 0.65 MJ/m | Cca-s1a,d1,a1 | 4 x 2 x 0.59 (AWG23) | arancia | 2 | 0.59 mm | FRNC/LSZH | 8.1 | 33.2 kg/km | 67 | 0.18 kWh/m | 1 | 1000 m tamburo |