FE180 E30
Safety cable, 0.6/1kV, Keram
halogen-free, with improved fire characteristics,
in accordance to SEV TP 20B/3C and CENELEC HD 604 S1 part 5.H
30 minutes system circuit integrity* with reference to DIN 4102-12
1 Conductor: solid/stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Sheath: FRNC/LSZH






Variantes de produits et stock
Télécharger
Numéro d'article | Inventaire | Produit | Nombres de coeurs | Diameter mm² | Diamètre de la gaine extérieure [mm] | Poids CU [kg/km] | Poids [kg/km] | Charge d'incendie[kWh/m] | Conducteur | Construction | GTIN / EAN |
---|---|---|---|---|---|---|---|---|---|---|---|
191118 | FE180 E30 2 x 1.5 | 2 | 1.5 | 7.8 | 29 | 102 | 0.22 | massif | LN | 40393910069662 | |
188360 | FE180 E30 2 x 1,5 | 2 | 1.5 | 7.8 | 29 | 102 | 0.22 | massif | 2L | 40393910072242 | |
191119 | FE180 E30 2 x 2.5 | 2 | 2.5 | 9 | 48 | 142 | 0.28 | massif | LN | 40393910069655 | |
190402 | FE180 E30 2 x 2,5 | 2 | 2.5 | 9 | 48 | 142 | 0.28 | massif | 2L | 40393910070996 | |
187180 | FE180 E30 3 x 1.5 | 3 | 1.5 | 8.3 | 43 | 121 | 0.25 | massif | LNPE | 40393910074499 | |
187184 | FE180 E30 3 x 2.5 | 3 | 2.5 | 9.5 | 72 | 169 | 0.31 | massif | LNPE | 40393910074451 | |
187187 | FE180 E30 3 x 4 | 3 | 4 | 11 | 115 | 243 | 0.41 | massif | LNPE | 40393910074420 | |
187189 | FE180 E30 3 x 6 | 3 | 6 | 12.5 | 173 | 329 | 0.51 | massif | LNPE | 40393910074406 | |
187182 | FE180 E30 4 x 1.5 | 4 | 1.5 | 9.1 | 58 | 147 | 0.29 | massif | 3LPE | 40393910074475 | |
190502 | FE180 E30 4 x 2.5 | 4 | 2.5 | 10.5 | 96 | 209 | 0.38 | massif | 3LPE | 40393910070828 | |
192352 | FE180 E30 4 x 4 | 4 | 4 | 12.2 | 154 | 304 | 0.49 | massif | 3LPE | 40393910067705 | |
192353 | FE180 E30 4 x 6 | 4 | 6 | 13.8 | 230 | 409 | 0.61 | massif | 3LPE | 40393910067699 | |
187183 | FE180 E30 5 x 1.5 | 5 | 1.5 | 9.9 | 72 | 177 | 0.35 | massif | 3LNPE | 40393910074468 | |
187186 | FE180 E30 5 x 2.5 | 5 | 2.5 | 11.6 | 120 | 255 | 0.47 | massif | 3LNPE | 40393910074437 | |
187188 | FE180 E30 5 x 4 | 5 | 4 | 13.4 | 192 | 371 | 0.61 | massif | 3LNPE | 40393910074413 | |
187190 | FE180 E30 5 x 6 | 5 | 6 | 15.2 | 288 | 504 | 0.76 | massif | 3LNPE | 40393910074390 | |
186267 | FE180 E30 7 x 1.5 | 7 | 1.5 | 10.8 | 100.8 | 220 | 0.41 | massif | 6LPE | 40393910076172 | |
186268 | FE180 E30 7 x 2.5 | 7 | 2.5 | 12.5 | 168 | 319 | 0.53 | massif | 6LPE | 40393910076165 | |
187201 | FE180 E30 7 x 6 | 7 | 6 | 16.7 | 403 | 644 | 0.89 | massif | 6LPE | 40393910074338 | |
187108 | FE180 E30 8 x 1.5 | 8 | 1.5 | 11.9 | 115 | 258 | 0.48 | massif | 7LPE | 40393910074680 | |
188345 | FE180 E30 10 x 1.5 | 10 | 1.5 | 13.8 | 144 | 319 | 0.69 | massif | 9LPE | 40393910072372 | |
186269 | FE180 E30 12 x 1.5 | 12 | 1.5 | 14.2 | 172.8 | 364 | 0.66 | massif | 11LPE | 40393910076158 | |
192479 | FE180 E30 12 x 2.5 | 12 | 2.5 | 16.7 | 288 | 536 | 0.88 | massif | 11LPE | 40393910067354 | |
187109 | FE180 E30 21 x 1.5 | 21 | 1.5 | 17.7 | 303 | 578 | 0.99 | massif | 20LPE | 40393910074673 | |
190412 | FE180 E30 27 x 1.5 | 27 | 1.5 | 20.4 | 389 | 752 | 1.30 | massif | 26LPE | 40393910070972 |
Spécifications techniques
Safety cables are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled.
Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used.
Permitted operating temperature at conductor of +90˚C.
Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used.
Permitted operating temperature at conductor of +90˚C.
Intégrité de l'isolation | FE 180 |
---|---|
Intégrité du circuit | E30 |
Température d'installation | -5 °C - +50 °C |
Température de fonctionnement | -45 °C - +90 °C |
Tension d'essai à 50 Hz | 3500 |
---|---|
Tension nominale | 0.6/1kV |
Rayon de courbure minimal lors de l'installation (câbles multiconducteurs) | 12 x D |
---|---|
Rayon de courbure minimal lors de l'installation (câble monoconducteur) | 15 x D |
Rayon de courbure minimal fixe (câbles multiconducteurs) | 12 x D |
Rayon de courbure minimal fixe (câble monoconducteur) | 15 x D |
Remarques sur le rayon de courbure | 50% reduction if installation at 30°C and with a template |
System Circuit Integrity is depemndent on installation method. |
Conducteur | Ame en cuivre nu, massive ou câblée, selon IEC 60228 et EN 60228 (16 mm2 selon VDE 0295) |
---|---|
Isolation du conducteur | Composé spécial, HD 604 S1 part 5 H # |
Couleurs des fils conducteurs | CENELEC HD 308 S2 |
Rembourrage | HD 604 S1 part 5 H |
Gaine extérieure | Compound, HD 604 S1 part 5 H |
Maintien de l'isolation | IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), BS 6387 C/W/Z, IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), AREI-RGIE Section 4.3.3 FR1 |
---|---|
Densité De Fumée | EN 61034-1/-2, IEC 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Section 4.3.3 SD, SEV TP 20B/3C 3.4.3 |
Zéro halogène, pas de gaz corrosifs | EN 60754-1/-2, IEC 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Section 4.3.3 SA, SEV TPV11 |
Propagation de flamme | IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Section 4.3.3 F1, SEV TP 20B/3C 3.4.1.1 |
Propagation de la flamme | EN 60332-3-24, IEC 60332-3-24, VDE 0482-332-3-24, AREI-RGIE Section 4.3.3 F2, SEV TP 20B/3C 3.4.1.3 |