(N)HXH FE180 E30-E60

Safety cable, 0.6/1kV, Keram
Halogen-free, with improved fire characteristics;
with reference to VDE 0266 and CENELEC HD 604 S1,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331,
System Circuit Integrity E30-E60* in accordance with DIN 4102-12

1 Conductor: solid/stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Sheath: FRNC/LSZH

07_Circuit 04_Propagation 05_Spread 06_Density 08_System 03_LS0H

Product variants & stock

Article No. Stock ProductDiameter mm²CU rate [kg/km]Weight [kg/km]ConductorConstructionPacking unitGTIN / EAN
194087
(N)HXH FE180 E30-E60 4x1,51.581281solid4L40393910064711
192844
28858440393910066302
192845
(N)HXH FE180 E30-E60 1 x 15015001590Lby the metre40393910066296
195828
1 x 24024002563Lby the metre40393910062090
195870
3 x 10100554LNPEby the metre40393910061925
195869
3 x 16160809LNPEby the metre40393910061932
195838
(OEM) 8670-U 4x2.5mm2 E30-E60 3LPE FE480 OEM) 8670-U 4x2.5mm2 E30-U 4x2.5mm2 E30 4 x 2.52.502903LPEby the metre40393910062045
195868
4 x 3535019293LPEby the metre40393910061949
195866
4 x 5050025983LPEby the metre40393910061963
195867
4 x 7070035783LPEby the metre40393910061956
195865
4 x 9595047853LPEby the metre40393910061970
195837
5 x 2.52.5018033LNPEby the metre40393910062052
195836
5 x 3535023853LNPEby the metre40393910062069
195834
(OEM) 8670-U 7x2.5mm2 E30-E60 6LPE FE780 OEM) 8670-U 7x2.5mm2 E30-U 7x2.5mm2 E30 7 x 2.52.504196LPEby the metre40393910062083

Technical specifications

Safety cables are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used. System Circuit Integrity is provided up to 400 V operating voltage. Permitted operating temperature at conductor of +90˚C.
Minimum bending radius permanent (multi core) 12 x D
Minimum bending during installation (single core) 15 x D
Minimum bending radius permanent (single core) 15 x D
Minimum bending during installation (multi core) 12 x D
Remarks bending radius 50% reduction if installation at 30°C and with a template
Circuit integrity FE 180
System circuit integrity E30-E60*
Installation temperature -5 °C - +50 °C
Operating temperature -45 °C - +90 °C
Test voltage at 50Hz 3500
Nominal voltage 0.6/1kV
* System Circuit Integrity is dependent on installation method
Conductor Bare copper, solid or stranded, IEC 60228 and EN 60228 (≥16 mm2: VDE 0295)
Insulation Special compound, HD 604 S1 part 5 H(≥16 mm2: double-layer insulation, special compound, VDE 0266 "HXI1")
Core colours CENELEC HD 308 S2(≥16 mm2: CENELEC HD 308 S2, VDE 0293)
Filler HD 604 S1 part 5 H(≥16 mm2: halogen-free polyolefin compound)
Outer sheath material Compound, HD 604 S1 part 5 H(16 mm2: polyolefin compound in accordance with VDE 0276-604, CENELEC HD 604 S1 "HM4", flame-retardant)
Circuit integrity IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), BS 6387 C/W/Z, IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), NBN 713-020 (Rf1), VDE 0482-200 (PH120), AREI-RGIE Art.104-FR1
System circuit integrity DIN 4102-12, AREI-RGIE Art.104-FR2
Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD, SEV TP 20B/3C 3.4.3
Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA, SEV TPV11
Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1, SEV TP 20B/3C 3.4.1.1
Flame spread IEC 60332-3-24, EN 60332-3-24, VDE 0482-332-3-24, AREI-RGIE Art.104-F2, SEV TP 20B/3C 3.4.1.3