JE-H(St)HRH...Bd FE180 E30-E90 fire alarm, black, B2ca

Fire alarm cable with steel wire braiding, max. 225V, Keram
halogen-free, with improved fire characteristics,
with reference to VDE 0815,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331, EN 50200,
System Circuit Integrity E30-E90* in accordance with DIN 4102-12
Fire behaviour according to EN 50575, EN 13601-6

1 Conductor: solid
2 Insulation: cross-linked polymer, halogen-free
3 Drain wire: copper, Ø 0.8 mm
4 Inner covering: plastic tape, halogen-free
5 Shielding: Al-laminated plastic foil, halogen-free
6 Inner sheath: FRNC/LS0H
7 Armouring: galvanised steel wire band
8 Sheath: FRNC/LS0H

06_Density 05_Spread 07_Circuit 03_LS0H 04_Propagation 08_System CPR_B2ca CPR_Cca CPR_Dca CPR_Eca

Product variants & stock

Article No. Stock ProductReaction to fireNumber of coresOuter sheath diameter [mm]CU rate [kg/km]Weight [kg/km]Fire load [kWh/m]Packing unitGTIN / EAN
19244300BZ
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 1x2x0.8 mmB2ca-s1a,d1,a128.81599.80.256by the metre40393910230178
19107100BZ
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 2x2x0.8 mmB2ca-s1a,d1,a129.325125.20.295by the metre40393910230536
19155400BZ
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 4x2x0.8 mmB2ca-s1a,d1,a1212.245190.40.437by the metre40393910230543
19407000BZ
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 8x2x0.8 mmB2ca-s1a,d1,a1218.485419.90.964by the metre40393910230222
19635400BZ
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 12x2x0.8 mmB2ca-s1a,d1,a1219.3126491.91.070by the metre40393910230253
19107000BZ
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 16x2x0.8 mmB2ca-s1a,d1,a1221.1166557.41.141by the metre40393910230529
19626500BZ
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 20x2x0.8 mmB2ca-s1a,d1,a1223.3206680.91.412by the metre40393910230239
19634700BZ
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 32x2x0.8 mmB2ca-s1a,d1,a1226.9326919.81.806by the metre40393910230246

Technical specifications

Cables with intrinsic fire resistance are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor and outdoor applications. The steel wire braiding serves as mechanical protection. The fire alarm cables correspond to the demands of System Circuit Integrity E30-E90* in accordance with DIN 4102-12. System Circuit Integrity is guaranteed at an operating voltage up to 110V.
Permitted operating temperature at conductor of +70°C.
Suitable according to VKF fire protection guideline in escape routes and in tunnels according to Astra guideline 13022.
operating capacity, 1km @ 800Hz 120
Test voltage 50Hz, core/core 500
peak voltage 225
Capacitive coupling 0,8 mm, 100m @ 800Hz 200
Maximum loop resistance 0,8 mm 73.2
Minimum insulation resistance 100
Test voltage 50Hz, core/screen 2000
Circuit integrity FE 180
System circuit integrity E90
Installation temperature -5 °C - +50 °C
Operating temperature -30 °C - +70 °C
Minimum bending during installation (multi core) 7.5 x D
Minimum bending radius permanent (multi core) 7.5 x D
Minimal crush resistance / 10cm 1000 N
System Circuit Integrity dependent on installation method.
Conductor Bare copper, solid, 0.8 mm diameter, VDE 0815
Insulation Fire-resistant, cross-linked, high-performance Keram special compound, EN 50290-2-36
Core colours VDE 0815
Shielding Al-laminated tape with copper drain wire Ø 0.8 mm
Inner sheath Flame retardant polyolefin compound, VDE 0819-107, EN 50290-2-27 and VDE 0250-214 "HM2"
Armouring (rodent protection) Galvanised steel wire braid
Outer sheath material Flame retardant polyolefin compound VDE 0819-107, EN 50290-2-27 and VDE 0250-214 "HM 2"
Outer sheath colour black
Circuit integrity IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), AREI-RGIE Section 4.3.3 FR1
System circuit integrity DIN 4102-12, AREI-RGIE Section 4.3.3 FR2
Reaction to fire EN 13501-6
Euroclass B2ca
Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Section 4.3.3 SD
Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Section 4.3.3 SA
Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Section 4.3.3 F1
Flame spread IEC 60332-3-22/-24, EN 60332-3-22/-24, VDE 0482-332-3-22/-24, AREI-RGIE Section 4.3.3 F2

Documentation