JE-H(St)HRH...Bd FE180 E30-E90 fire alarm, black, B2ca
Fire alarm cable with steel wire braiding, max. 225V, Keram
halogen-free, with improved fire characteristics,
with reference to VDE 0815,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331, EN 50200,
System Circuit Integrity E30-E90* in accordance with DIN 4102-12
Fire behaviour according to EN 50575, EN 13601-6
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 1x2x0.8 mm
B2ca-s1a,d1,a1
2
8.8
15
99.8
0.256
by the metre
40393910230178
19107100BZ
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 2x2x0.8 mm
B2ca-s1a,d1,a1
2
9.3
25
125.2
0.295
by the metre
40393910230536
19155400BZ
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 4x2x0.8 mm
B2ca-s1a,d1,a1
2
12.2
45
190.4
0.437
by the metre
40393910230543
19407000BZ
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 8x2x0.8 mm
B2ca-s1a,d1,a1
2
18.4
85
419.9
0.964
by the metre
40393910230222
19635400BZ
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 12x2x0.8 mm
B2ca-s1a,d1,a1
2
19.3
126
491.9
1.070
by the metre
40393910230253
19107000BZ
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 16x2x0.8 mm
B2ca-s1a,d1,a1
2
21.1
166
557.4
1.141
by the metre
40393910230529
19626500BZ
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 20x2x0.8 mm
B2ca-s1a,d1,a1
2
23.3
206
680.9
1.412
by the metre
40393910230239
19634700BZ
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 32x2x0.8 mm
B2ca-s1a,d1,a1
2
26.9
326
919.8
1.806
by the metre
40393910230246
Technical specifications
Cables with intrinsic fire resistance are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor and outdoor applications. The steel wire braiding serves as mechanical protection. The fire alarm cables correspond to the demands of System Circuit Integrity E30-E90* in accordance with DIN 4102-12. System Circuit Integrity is guaranteed at an operating voltage up to 110V.
Permitted operating temperature at conductor of +70°C.
Suitable according to VKF fire protection guideline in escape routes and in tunnels according to Astra guideline 13022.
operating capacity, 1km @ 800Hz
120
Test voltage 50Hz, core/core
500
peak voltage
225
Capacitive coupling 0,8 mm, 100m @ 800Hz
200
Maximum loop resistance 0,8 mm
73.2
Minimum insulation resistance
100
Test voltage 50Hz, core/screen
2000
Circuit integrity
FE 180
System circuit integrity
E90
Installation temperature
-5 °C - +50 °C
Operating temperature
-30 °C - +70 °C
Minimum bending during installation (multi core)
7.5 x D
Minimum bending radius permanent (multi core)
7.5 x D
Minimal crush resistance / 10cm
1000
N
System Circuit Integrity dependent on installation method.
Conductor
Bare copper, solid, 0.8 mm diameter, VDE 0815
Insulation
Fire-resistant, cross-linked, high-performance Keram special compound, EN 50290-2-36
Core colours
VDE 0815
Shielding
Al-laminated tape with copper drain wire Ø 0.8 mm
Inner sheath
Flame retardant polyolefin compound, VDE 0819-107, EN 50290-2-27 and VDE 0250-214 "HM2"
Armouring (rodent protection)
Galvanised steel wire braid
Outer sheath material
Flame retardant polyolefin compound VDE 0819-107, EN 50290-2-27 and VDE 0250-214 "HM 2"