J-H(St)H...Bd fire alarm

Fire alarm cable, max. 300V
halogen-free, with improved fire characteristics,
VDE 0815

1 Conductor: solid
2 Insulatio: halogen-free polymer compound
3 Separator: plastic tape
4 Drain wire: tinned copper
5 Shielding: Al-laminated plastic foil
6 Sheath: FRNC/LSZH

07_Circuit- 04_Propagation 05_Spread 06_Density 08_System- 03_LS0H

Product variants & stock

Article No. Stock ProductOuter sheath colourNumber of coresOuter sheath diameter [mm]CU rate [kg/km]Weight [kg/km]Fire load [kWh/m]Packing unitGTIN / EAN
157892
J-H(St)H...Bd fire alarm 2x2x0.8 mmred26.525590.16by the metre40393910207637
157893
J-H(St)H...Bd fire alarm 4x2x0.8 mmred28.5451110.29by the metre40393910207620
157894
J-H(St)H...Bd fire alarm 6x2x0.8 mmred210.5651320.35by the metre40393910207613
157895
J-H(St)H...Bd fire alarm 10x2x0.8 mmred2131062160.55by the metre40393910207606
1172017
J-H(St)H...Bd fire alarm 20x2x0.8 mmred215.52065081.21by the metre40393910107104
1172018
J-H(St)H...Bd fire alarm 30x2x0.8 mmred216.33075991.36by the metre40393910107098
1172019
J-H(St)H...Bd fire alarm 40x2x0.8 mmred216.54077871.67by the metre40393910107081
1172021
J-H(St)H...Bd fire alarm 80x2x0.8 mmred231.580914763.18by the metre40393910107074
1172022
J-H(St)H...Bd fire alarm 100x2x0.8 mmred238101018054.07by the metre40393910107067

Technical specifications

Installation cable with electrostatic shield for areas vulnerable to fire and with high concentration of people and property value. For ICT systems for lossless data and signal transmission. Suitable for laying in dry and humid rooms, on-wall and in-wall, also for outdoor use.
No underground laying. Not to be used for high-voltage transmission.
Permitted operating temperature at conductor of +70°C.
operating capacity, 1km @ 800Hz 120
Maximum loop resistance 0,6 mm 130
Maximum loop resistance 0,8 mm 73.2
Test voltage 50Hz, core/screen 800
Minimum insulation resistance 100
Capacitive coupling 0,8 mm, 100m @ 800Hz 200
Capacitive coupling 0,6 mm, 100m @ 800Hz 300
Test voltage 50Hz, core/core 800
peak voltage 300
Minimum bending radius permanent (multi core) 2.5 x D
Minimum bending during installation (multi core) 7.5 x D
Circuit integrity No
System circuit integrity No
Installation temperature -5 °C - +50 °C
Operating temperature -30 °C - +70 °C
Additional dimensions available on request.
Conductor Bare copper, solid, 0.6 or 0.8 mm diameter
Insulation Halogen-free polymer compound, EN 50290-2-26
Core colours VDE 0815
Shielding Al-laminated plastic foil with drain wire, copper tinned
Outer sheath material Halogen-free polymer compound, EN 50290-2-27
Stranding Cores twisted to star-quads and quads to units
Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Section 4.3.3 SD
Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Section 4.3.3 SA
Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Section 4.3.3 F1
Flame spread IEC 60332-3-24, EN 60332-3-24, AREI-RGIE Section 4.3.3 F2