(N)HXCH FE180 E90 B2ca

Safety cable, 0.6/1kV, Keram
halogen-free, with improved fire characteristics,
with reference to VDE 0266 and CENELEC HD 604 S1,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331,
System Circuit Integrity E90 in accordance with DIN 4102-12
Reaction to fire according to EN 13501-6

1 Conductor: solid/stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Concentric conductor: bare copper wire
6 Reinforcing helix: bare copper tape
7 Separator: plastic tape
8 Sheath: FRNC/LSZH

05_Spread 04_Propagation 03_LS0H 07_Circuit 06_Density 08_System

Product variants & stock

Article No. Stock ProductReaction to fireOuter sheath colourDiameter mm²Outer sheath diameter [mm]CU rate [kg/km]Weight [kg/km]Fire load [kWh/m]ConductorConstructionPacking unitGTIN / EAN
18740800BZ
(N)HXCH FE180 E90 3 x 50/25B2ca-s1a,d1,a1orange50/2532.5172325452.729stranded3Lby the metre40393910036961
19648300BZ
(N)HXCH FE180 E90 3 x 50/50B2ca-s1a,d1,a1orange50/5034.3193329323.028stranded3Lby the metre
18741100BZ
(N)HXCH FE180 E90 3 x 120/70B2ca-s1a,d1,a1orange120/7045.3423656885.112stranded3Lby the metre40393910036930
18741200BZ
(N)HXCH FE180 E90 3 x 150/70B2ca-s1a,d1,a1orange150/7050510069115.889stranded3Lby the metre40393910036923
17241700BZ
(N)HXCH FE180 E90 3 x 35/16B2ca-s1a,d1,a1orange35/1629119019412.267stranded3Lby the metre40393910043600
18740900BZ
(N)HXCH FE180 E90 3 x 70/35B2ca-s1a,d1,a1orange70/3537.6241035363.542stranded3Lby the metre40393910036954
18741000BZ
(N)HXCH FE180 E90 3 x 95/50B2ca-s1a,d1,a1orange95/5041.9329645814.285stranded3Lby the metre40393910036947
18613700BZ
(N)HXCH FE180 E90 4 x 120/70B2ca-s1a,d1,a1orange120/7050.1538870785.858stranded3LNby the metre40393910039702
18613800BZ
(N)HXCH FE180 E90 4 x 150/70B2ca-s1a,d1,a1orange150/7055.3654086317.11stranded3LNby the metre40393910039689
18613100BZ
(N)HXCH FE180 E90 4 x 16/16B2ca-s1a,d1,a1orange16/1625.379613961.772stranded3LNby the metre40393910039764
18613900BZ
(N)HXCH FE180 E90 4 x 185/95B2ca-s1a,d1,a1orange185/9560.88159107278.61stranded3LNby the metre40393910039665
18614000BZ
(N)HXCH FE180 E90 4 x 240/120B2ca-s1a,d1,a1orange240/12069.2105461394910.885stranded3LNby the metre40393910039658
18613200BZ
(N)HXCH FE180 E90 4 x 25/16B2ca-s1a,d1,a1orange25/1628.9114218952.568stranded3LNby the metre40393910039757
18613300BZ
(N)HXCH FE180 E90 4 x 35/16B2ca-s1a,d1,a1orange35/1631.6152623782.568stranded3LNby the metre40393910039740
18613400BZ
(N)HXCH FE180 E90 4 x 50/25B2ca-s1a,d1,a1orange50/2536.7220332453.374stranded3LNby the metre40393910039733
18613500BZ
(N)HXCH FE180 E90 4 x 70/35B2ca-s1a,d1,a1orange70/3541.3308243714.08stranded3LNby the metre40393910039726
18613600BZ
(N)HXCH FE180 E90 4 x 95/50B2ca-s1a,d1,a1orange95/5046.4420857125.179stranded3LNby the metre40393910039719
18607100BZ
(N)HXCH FE180 E90 3 x 1.5/1.5B2ca-s1a,d1,a1orange1.5/1.513.2662460.599solid3Lby the metre40393910039795
18619500BZ
(N)HXCH FE180 E90 3 x 2.5/2.5B2ca-s1a,d1,a1orange2.5/2.514.11043030.784solid3Lby the metre40393910039207
18619700BZ
(N)HXCH FE180 E90 3 x 4/4B2ca-s1a,d1,a1orange4/415.61614000.771solid3Lby the metre40393910039184
18727800BZ
(N)HXCH FE180 E90 3 x 6/6B2ca-s1a,d1,a1orange6/616.92405210.921solid3Lby the metre40393910037173
18607200BZ
(N)HXCH FE180 E90 4 x 1.5/1.5B2ca-s1a,d1,a1orange1.5/1.514.1812800.677solid3LNby the metre40393910039788
18620000BZ
(N)HXCH FE180 E90 4 x 10/10B2ca-s1a,d1,a1orange10/1020.15048581.25solid3LNby the metre40393910039153
18619600BZ
(N)HXCH FE180 E90 4 x 2.5/2.5B2ca-s1a,d1,a1orange2.5/2.515.11283500.754solid3LNby the metre40393910039191
18619800BZ
(N)HXCH FE180 E90 4 x 4/4B2ca-s1a,d1,a1orange4/416.72004640.87solid3LNby the metre40393910039177
18619900BZ
(N)HXCH FE180 E90 4 x 6/6B2ca-s1a,d1,a1orange6/618.12976121.051solid3LNby the metre40393910039160
18607302BZ
(N)HXCH FE180 E90 7 x 1.5/2.5B2ca-s1b,d1,a1orange1.5/2.516.11333900.884solid7Lby the metre40393910039771
19109602BZ
(N)HXCH FE180 E90 7 x 2.5/2.5B2ca-s1b,d1,a1orange2.5/2.517.32004840.994solid7Lby the metre40393910031782
18741502BZ
(N)HXCH FE180 E90 12 x 1.5/2.5B2ca-s1b,d1,a1orange1.5/2.520.2205.85891.308solid12Lby the metre40393910036916
19648200BZ
(N)HXCH FE180 E90 3 x 35/35B2ca-s1a,d1,a1orange35/3530.9135822032.484stranded3Lby the metre

Technical specifications

Cables with intrinsic fire resistance are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used. These cables correspond to the demands of System Circuit Integrity E90* in accordance with DIN 4102-12. System Circuit Integrity is guaranteed at an operating voltage up to 400V. Permitted operating temperature at conductor of +90˚C. Suitable according to VKF fire protection guideline in escape routes and in tunnels according to Astra guideline 13022.
Minimum bending radius permanent (multi core) 12 x D
Minimum bending during installation (multi core) 12 x D
Circuit integrity (FE180) FE 180
System circuit integrity E90
Installation temperature -5 °C - +50 °C
Operating temperature -45 °C - +90 °C
Test voltage at 50Hz 4000
Nominal voltage 0.6/1kV
For use in critical fire safety infrastructure (in compliance with VKF, ASTRA, Tunnels Directive, etc.), particularly in escape routes and emergency lines.
System Circuit Integrity is dependent on installation method.
Conductor Bare copper, solid or stranded, IEC 60228 and EN 60228 (VDE 0295)
Insulation Double insulation, cross-linked, high-performance Keram special compound, VDE 0266 "HXI1"
Core colours CENELEC HD 308 S2, VDE 0293
Separator Plastic tape
Filler Halogen-free compound or plastic tape
Concentric conductor Bare copper wires with reinforced helix
Outer sheath material Flame retardant Polyolefin compound, CENELEC HD 604 S1 and VDE 0276-604 "HM4"
Outer sheath colour orange
Circuit integrity (FE180) IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), AREI-RGIE Art.104-FR1
System circuit integrity DIN 4102-12, VdS 3423 (Single-core more than 16.0 mm²), AREI-RGIE Art.104-FR2
Reaction to fire EN 13501-6
Euroclass B2ca
Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA
Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1
Flame spread IEC 60332-3-22/-24, EN 60332-3-22/-24, VDE 0482-332-3-22/-24, AREI-RGIE Art.104-F2

Documentation