JE-H(St)HRH...Bd FE180 E30-E90 fire alarm, black

Fire alarm cable with steel wire braiding, max. 225V, Keram
halogen-free, with improved fire characteristics,
with reference to VDE 0815,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331, EN 50200,
System Circuit Integrity E30-E90* in accordance with DIN 4102-12

1 Conductor: solid
2 Insulation: cross-linked polymer, halogen-free
3 Drain wire: copper, Ø 0.8 mm
4 Inner covering: plastic tape, halogen-free
5 Shielding: Al-laminated plastic foil, halogen-free
6 Inner sheath: FRNC/LS0H
7 Armouring: galvanised steel wire band
8 Sheath: FRNC/LS0H

07_Circuit 04_Propagation 05_Spread 06_Density 08_System 03_LS0H

Product variants & stock

Article No. Stock ProductOuter sheath colourOuter sheath diameter [mm]CU rate [kg/km]Weight [kg/km]Fire load [kWh/m]Packing unitGTIN / EAN
191071
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 2x2x0.8 mmblack9.3251250.26by the metre40393910069945
191554
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 4x2x0.8 mmblack12451910.39by the metre40393910069211
194070
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 8x2x0.8 mmblack18.2854190.93by the metre40393910064759
196354
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 12x2x0.8 mmblack19.11264901.01by the metre40393910061192
191070
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 16x2x0.8 mmblack20.51665571.17by the metre40393910069952
196265
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 20x2x0.8 mmblack22.32066801.32by the metre40393910061536
196347
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 32x2x0.8 mmblack26.73269121.72by the metre40393910061222

Technical specifications

Cables with intrinsic fire resistance are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor and outdoor applications. The steel wire braiding serves as mechanical protection. The fire alarm cables correspond to the demands of System Circuit Integrity E30-E90* in accordance with DIN 4102-12. System Circuit Integrity is guaranteed at an operating voltage up to 110V. Permitted operating temperature at conductor of +70°C.
operating capacity, 1km @ 800Hz 120
Maximum loop resistance 0,8 mm 73.2
Test voltage 50Hz, core/screen 2000
Minimum insulation resistance 100
Capacitive coupling 0,8 mm, 100m @ 800Hz 200
Test voltage 50Hz, core/core 500
peak voltage 225
Minimum bending radius permanent (multi core) 7.5 x D
Minimum bending during installation (multi core) 7.5 x D
Minimal crush resistance / 10cm 1000 N
Circuit integrity (FE180) FE 180
System circuit integrity E90
Installation temperature -5 °C - +50 °C
Operating temperature -30 °C - +70 °C
System Circuit Integrity dependent on installation method.
Conductor Bare copper, solid, 0.8 mm diameter, VDE 0815
Insulation Fire-resistant, cross-linked, high-performance Keram special compound, EN 50290-2-36
Core colours VDE 0815
Shielding Al-laminated tape with copper drain wire Ø 0.8 mm
Inner sheath Flame retardant polyolefin compound, VDE 0819-107, EN 50290-2-27 and VDE 0250-214 "HM2"
Armouring (rodent protection) Galvanised steel wire braid
Outer sheath material Flame retardant polyolefin compound VDE 0819-107, EN 50290-2-27 and VDE 0250-214 "HM 2"
Circuit integrity (FE180) IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), BS 6387 C/W/Z, IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), AREI-RGIE Art.104-FR1
System circuit integrity DIN 4102-12, AREI-RGIE Art.104-FR2
Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA
Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1
Flame spread IEC 60332-3-22/-24, EN 60332-3-22/-24, VDE 0482-332-3-22/-24, AREI-RGIE Art.104-F2

Documentation