(N)HXH CL FE180 E30-E60

Safety cable, 0.6/1kV armoured with rodent protection, Keram
halogen-free, with improved fire characteristics,
with reference to VDE 0266 and CENELEC HD 604 S1,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331,
System Circuit Integrity E30-E60* in accordance with DIN 4102-12

1 Conductor: solid/stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Inner sheath: Polyolefin, flame retardant, low smoke, zero halogen
6 Armouring: galvanised steel tape
7 Sheath: FRNC/LSZH

07_Circuit 04_Propagation 05_Spread 06_Density 08_System 03_LS0H

Product variants & stock

Article No. Stock ProductDiameter mm²Outer sheath diameter [mm]CU rate [kg/km]Weight [kg/km]Fire load [kWh/m]ConductorConstructionGTIN / EAN
191612
(N)HXH-O CL FE180 E30-E60 2 x 4417774501.13solidLN40393910069044
192350
(N)HXH-O CL FE180 E30-E60 2 x 1.51.514.9293330.94solidLN40393910067729
187562
(N)HXH-O CL FE180 E30-E60 2 x 2.52.516483801.02solidLN40393910073614
187563
(N)HXH-O CL FE180 E30-E60 2 x 66181155271.25solidLN40393910073607
191107
(N)HXH-J CL FE180 E30-E60 3 x 1.51.516433611.00solidLNPE40393910069730
186940
(N)HXH-J CL FE180 E30-E60 3 x 2.52.516.3724221.10solidLNPE40393910075397
192351
(N)HXH-J CL FE180 E30-E60 3 x 44181155091.22solidLNPE40393910067712
188326
(N)HXH-J CL FE180 E30-E60 3 x 66191736021.35solidLNPE40393910072433
191597
(N)HXH-J CL FE180 E30-E60 3 x 1010212887771.54solidLNPE40393910069129
190590
(N)HXH-J CL FE180 E30-E60 4 x 2.52.518964751.22solid3LPE40393910070583
191102
(N)HXH-J CL FE180 E30-E60 4 x 44191545851.36solid3LPE40393910069761
192593
(N)HXH-J CL FE180 E30-E60 4 x 66202307031.51solid3LPE40393910066968
192594
(N)HXH-J CL FE180 E30-E60 4 x 1010223849301.76solid3LPE40393910066951
192347
(N)HXH-J CL FE180 E30-E60 5 x 1.51.518724631.25solid3LNPE40393910067736
188117
(N)HXH-J CL FE180 E30-E60 5 x 2.52.5191205451.38solid3LNPE40393910072945
188118
(N)HXH-J CL FE180 E30-E60 5 x 44201926751.54solid3LNPE40393910072938
186941
(N)HXH-J CL FE180 E30-E60 5 x 66212888181.72solid3LNPE40393910075380
186942
(N)HXH-J CL FE180 E30-E60 5 x 10102448010841.98solid3LNPE40393910075373
190525
(N)HXH-J CL FE180 E30-E60 5 x 16162676815312.53stranded3LNPE40393910070774
190529
(N)HXH-J CL FE180 E30-E60 5 x 353535168028013.85stranded3LNPE40393910070736
191565
(N)HXH-J CL FE180 E30-E60 5 x 505039240036784.83stranded3LNPE40393910069198
188094
(N)HXH-J CL FE180 E30-E60 6 x 44202306931.74solid5LPE40393910073157
185232
(N)HXH-J CL FE180 E30-E60 7 x 1.51.5191015291.38solid6LPE40393910077308
185245
(N)HXH-J CL FE180 E30-E60 7 x 44212697971.71solid6LPE40393910077216
185247
(N)HXH-J CL FE180 E30-E60 7 x 66234039771.9solid6LPE40393910077209
185248
(N)HXH-J CL FE180 E30-E60 7 x 10102567213282.2solid6LPE40393910077193
188095
(N)HXH-J CL FE180 E30-E60 8 x 44233078341.91solid7LPE40393910073140
185239
(N)HXH-J CL FE180 E30-E60 12 x 2.52.5232889422.13solidLPE40393910077254
185233
(N)HXH-J CL FE180 E30-E60 16 x 1.51.5242309222.24solid15LPE40393910077292
185235
(N)HXH-J CL FE180 E30-E60 30 x 1.51.53043214023.25solid29LPE40393910077278
185241
(N)HXH-J CL FE180 E30-E60 30 x 2.52.53372018263.81solid29LPE40393910077230
188327
(N)HXH-J CL FE180 E30-E60 3 x 16162446110741.93strandedLNPE40393910072426
186980
(N)HXH-J CL FE180 E30-E60 4 x 16162561412932.20stranded3LPE40393910074994
186981
(N)HXH-J CL FE180 E30-E60 4 x 25252996018142.78stranded3LPE40393910074987
186982
(N)HXH-J CL FE180 E30-E60 4 x 353532134422963.16stranded3LPE40393910074970
190589
(N)HXH-J CL FE180 E30-E60 4 x 505036192030304.02stranded2LNPE40393910070590
192428
(N)HXH-J CL FE180 E30-E60 4 x 707040268840155.05stranded3LPE40393910067590
192429
(N)HXH-J CL FE180 E30-E60 4 x 959546364853436.52stranded3LPE40393910067583
192430
(N)HXH-J CL FE180 E30-E60 4 x 12012049460864337.26stranded3LPE40393910067576
187154
(N)HXH-J CL FE180 E30-E60 5 x 16162776814522.53stranded3LNPE40393910074574
186984
(N)HXH-J CL FE180 E30-E60 5 x 252531120021683.23stranded3LNPE40393910074963
187132
(N)HXH-J CL FE180 E30-E60 5 x 353535168027023.85stranded3LNPE40393910074611
187131
(N)HXH-J CL FE180 E30-E60 5 x 505039240036134.83stranded3LNPE40393910074628
194049
(N)HXH-J CL FE180 E30-E60 5 x 707045336049996.05stranded3LNPE40393910064773
196400
(N)HXH-J CL FE180 E30-E60 16 x 4427.5614.41414solid15LPE40393910061055

Technical specifications

Cables with intrinsic fire resistance are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used. These cables correspond to the demands of Circuit Integrity E30-E60* in accordance with DIN 4102-12. Circuit Integrity is guaranteed at an operating voltage up to 400V. Permitted operating temperature at conductor of +90˚C.
Minimum bending radius permanent (multi core) 12 x D
Minimum bending during installation (single core) 15 x D
Minimum bending radius permanent (single core) 15 x D
Minimum bending during installation (multi core) 12 x D
Circuit integrity (FE180) FE 180
System circuit integrity E30-E60*
Installation temperature -5 °C - +50 °C
Operating temperature -45 °C - +90 °C
Test voltage at 50Hz 4000
Nominal voltage 0.6/1kV
System Circuit Integrity is dependent on installation method.
Conductor Bare copper, solid or stranded, IEC 60228 and EN 60228 (VDE 0295)
Insulation Double insulation, cross-linked, high-performance Keram special compound, VDE 0266 "HXI1"
Core colours CENELEC HD 308 S2, VDE 0293
Filler Flame retardant, halogen-free thermoplastic compound
Inner sheath Flame retardant Polyolefin compound,CENELEC HD 604 S1 and VDE 0276-604 "HM4"
Armouring (rodent protection) Single-core cable with copper tape (CLCU) and multicore cable with galvanised steel tape (CL)
Outer sheath material Flame retardant Polyolefin compound, CENELEC HD 604 S1 and VDE 0276-604 "HM4"
Circuit integrity (FE180) IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), BS 6387 C/W/Z, IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), AREI-RGIE Art.104-FR1
System circuit integrity DIN 4102-12, AREI-RGIE Art.104-FR2
Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA
Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1
Flame spread IEC 60332-3-22/-24, EN 60332-3-22/-24, VDE 0482-332-3-22/-24, AREI-RGIE Art.104-F2

Documentation