Armoured Standard Fire Safety Cable

Fire alarm cable, 300/500V, with steel wire braiding
halogen-free, with improved fire characteristics,
with reference to BS 7629-1

1 Conductor: solid or stranded
2 Insulation: fire resistant special compound
3 Drain wire: tinned copper
4 Inner covering: glass fibre tape
5 Shielding: Alu-laminated tape
6 Inner sheath: Polyolefin compound
7 Armouring: galvanised steel wire band
8 Sheath: FRNC/LSZH

07_Circuit 04_Propagation 05_Spread 06_Density 08_System- 03_LS0H

Product variants & stock

Article No. Stock ProductOuter sheath colourDiameter mm²Outer sheath diameter [mm]CU rate [kg/km]Weight [kg/km]Fire load [kWh/m]GTIN / EAN
194031
Armoured Standard Fire Safety Cablered1.511.5481840.4040393910064834

Technical specifications

Armoured cable for fire alarm systems and emergency lighting for permament installation in buildings. Permitted operating temperature at conductor of +90˚C.
Minimum bending radius permanent (multi core) 6 x D
Minimum bending during installation (multi core) 6 x D
Test voltage at 50Hz 2000
Nominal voltage 300/500V
Additional dimensions available on request.
Conductor Bare copper, solid or stranded in accordance with IEC 60228 and EN 60228
Insulation Special compound, BS EN 50363-5
Core colours 2 cores + earth: blue, brown; 3 cores + earth: brown, black, grey, 4 cores + earth: blue, brown, black, grey
Shielding Al-laminated tape and tinned copper drain wire, IEC 60228 class 1or 2, EN 60228
Inner sheath Polyolefin compound
Armouring (rodent protection) Stahldrahtgeflecht mit ca. 70% Überdeckung
Outer sheath material Polyolefin compound, BS 7655-6.1, LTS3
Installation temperature -5 °C - +50 °C
Operating temperature -15 °C - +90 °C
Circuit integrity (FE180) IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), BS 6387 C/W/Z, IEC 60331-2 (120 minutes), BS EN 50200 Annex E, VDE 0482-200 (PH120), AREI-RGIE Art.104-FR1, BS EN 50200
Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA
Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1
Flame spread IEC 60332-3-22/-24, EN 60332-3-22/-24, VDE 0482-332-3-22/-24, AREI-RGIE Art.104-F2

Documentation