FE180 flex

Control cable flex, 300/500V, Keram
halogen-free, with improved fire characteristics,
with reference to SEV TP 20B/3C and CENELEC HD 604 S1 part 5.H

1 Conductor: stranded
2 Fire barrier: high-performance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Sheath: FRNC / LSZH

07_Circuit 04_Propagation 05_Spread 06_Density 08_System- 03_LS0H

Product variants & stock

Article No. Stock ProductDiameter mm²Outer sheath diameter [mm]CU rate [kg/km]Weight [kg/km]Fire load [kWh/m]ConstructionGTIN / EAN
188335
FE180 flex 3 x 1.51.58.5431230.27LNPE40393910072419
187554
FE180 flex 5 x 1.51.510.3721820.403LNPE40393910073645
187179
FE180 flex 5 x 2.52.512.11202710.553LNPE40393910074505
192367
FE180 flex 7 x 1.51.5111012220.446LPE40393910067620
185228
FE180 flex 8 x 1.51.512.41152730.566LNPE40393910077315
191059
FE180 flex 12 x 1.51.5141733130.7211LPE40393910070033
191060
FE180 flex 16 x 1.51.5162314100.8915LPE40393910070026
191061
FE180 flex 21 x 1.51.5183035271.1020LPE40393910070019

Technical specifications

Safety cables are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used. Permitted operating temperature at conductor of +90˚C.
Minimum bending radius permanent (multi core) 4 x D
Minimum bending during installation (multi core) 6 x D
Circuit integrity (FE180) FE 180
Installation temperature -5 °C - +50 °C
Operating temperature -45 °C - +90 °C
Test voltage at 50Hz 2000
Nominal voltage 300/500V
Additional dimensions available on request.
Conductor Bare copper, stranded, IEC 60228 class 5, EN 60228
Insulation Special compound, HD 604 S1 part 5 H
Core colours CENELEC HD 308 S2
Filler HD 604 S1 part 5 H
Outer sheath material Compound, HD 604 S1 part 5 H
Circuit integrity (FE180) IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), BS 6387 C/W/Z, IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), AREI-RGIE Art.104-FR1
Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD, SEV TP 20B/3C 3.4.3
Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA, SEV TPV11
Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1, SEV TP 20B/3C 3.4.1.1
Flame spread IEC 60332-3-24, EN 60332-3-24, VDE 0482-332-3-24, AREI-RGIE Art.104-F2, SEV TP 20B/3C 3.4.1.3