1 Conductor: stranded
2 Fire barrier: high-performance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Sheath: FRNC / LSZH
Product variants & stock
Article No.
Stock
Product
Diameter mm²
Outer sheath diameter [mm]
CU rate [kg/km]
Weight [kg/km]
Fire load [kWh/m]
Construction
GTIN / EAN
188335
FE180 flex 3 x 1.5
1.5
8.5
43
123
0.27
LNPE
40393910072419
187554
FE180 flex 5 x 1.5
1.5
10.3
72
182
0.40
3LNPE
40393910073645
187179
FE180 flex 5 x 2.5
2.5
12.1
120
271
0.55
3LNPE
40393910074505
192367
FE180 flex 7 x 1.5
1.5
11
101
222
0.44
6LPE
40393910067620
185228
FE180 flex 8 x 1.5
1.5
12.4
115
273
0.56
6LNPE
40393910077315
191059
FE180 flex 12 x 1.5
1.5
14
173
313
0.72
11LPE
40393910070033
191060
FE180 flex 16 x 1.5
1.5
16
231
410
0.89
15LPE
40393910070026
191061
FE180 flex 21 x 1.5
1.5
18
303
527
1.10
20LPE
40393910070019
Technical specifications
Safety cables are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled.
Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used.
Permitted operating temperature at conductor of +90˚C.
Minimum bending radius permanent (multi core)
4 x D
Minimum bending during installation (multi core)
6 x D
Circuit integrity (FE180)
FE 180
Installation temperature
-5 °C - +50 °C
Operating temperature
-45 °C - +90 °C
Test voltage at 50Hz
2000
Nominal voltage
300/500V
Additional dimensions available on request.
Conductor
Bare copper, stranded, IEC 60228 class 5, EN 60228