Installation cable with electrostatic shield for areas vulnerable to fire and with high concentration of people and property value. For ICT systems for lossless data and signal transmission. Suitable for laying in dry and humid rooms, on-wall and in-wall, also for outdoor use.
No underground laying. Not to be used for high-voltage transmission.
Permitted operating temperature at conductor of +70°C.
operating capacity, 1km @ 800Hz
120
Maximum loop resistance 0,6 mm
130
Maximum loop resistance 0,8 mm
73.2
Test voltage 50Hz, core/screen
800
Minimum insulation resistance
100
Capacitive coupling 0,8 mm, 100m @ 800Hz
200
Capacitive coupling 0,6 mm, 100m @ 800Hz
300
Test voltage 50Hz, core/core
800
peak voltage
300
Minimum bending radius permanent (multi core)
2.5 x D
Minimum bending during installation (multi core)
7.5 x D
Circuit integrity (FE180)
No
System circuit integrity
No
Installation temperature
-5 °C - +50 °C
Operating temperature
-30 °C - +70 °C
Keyfeatures
halogen-free, with improved fire characteristics,
VDE 0815
Note
Additional dimensions available on request.
Conductor
Bare copper, solid, 0.6 or 0.8 mm diameter
Insulation
Halogen-free polymer compound, EN 50290-2-26
Core colours
VDE 0815
Shielding
Al-laminated plastic foil with drain wire, copper tinned
Outer sheath material
Halogen-free polymer compound, EN 50290-2-27
Stranding
Cores twisted to star-quads and quads to units
Smoke density
IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
Zero halogen no corrosive gases
IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA
Flame propagation
IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1
Flame spread
IEC 60332-3-24, EN 60332-3-24, AREI-RGIE Art.104-F2