FO Outdoor ZGGT BL / A-DQ(ZN)B2Y

Basic Line Euroclass Fca
central loose tube, metal-free,
longitudinally watertight, rodent protection

1 ≤ 24 fibres
2 Loose tube
3 Glass armour
4 Ripcord
5 HDPE sheath

04_Propagation- 05_Spread- 06_Density- 08_System- 03_LS0H CPR_Fca

Product variants & stock

Article No. Stock Loose tube constructionFibres per loose tubeNumber of used loose tubesProductReaction to fireOuter sheath colourNumber of fibresFibre typeFibre categoryOuter sheath diameter [mm]Bending radius [mm]CU rate [kg/km]Weight [kg/km]Tensile load [N]Crush resistance short term [N]Crush resistance continuous [N]Fire load [kWh/m]Packing unitGTIN / EAN
19613400FZ
121FO Outdoor BL 1x2Fcablack/orange2E9/125 G.652.D OS2OS27.31100481000500020000.418by the metre40393910019704
19129200FZ
141FO Outdoor BL 1x4Fcablack/orange4E9/125 G.652.D OS2OS27.31100481000500020000.418by the metre40393910031287
19125600FZ
161FO Outdoor BL 1x6Fcablack/orange6E9/125 G.652.D OS2OS27.31100481000500020000.418by the metre40393910031430
19118800FZ
161FO Outdoor BL 1x6Fcablack/orange6G50/125 OM3OM37.31100481000500020000.418by the metre40393910031645
18650000FZ
181FO Outdoor BL 1x8Fcablack/orange8E9/125 G.652.D OS2OS27.31100481000500020000.418by the metre40393910038798
19019200FZ
1121FO Outdoor BL 1x12Fcablack/orange12E9/125 G.652.D OS2OS27.31100481000500020000.418by the metre40393910033441
19262600FZ
1121FO Outdoor BL 1x12Fcablack/orange12E9/125 G.652.D BLOOS27.31100481000500020000.418by the metre40393910027235
19119000FZ
1121FO Outdoor BL 1x12Fcablack/orange12G50/125 OM3OM37.31100481000500020000.418by the metre40393910031638
19019300FZ
1241FO Outdoor BL 1x24Fcablack/orange24E9/125 G.652.D OS2OS281200561000500020000.491by the metre40393910033434

Technical specifications

Metal-free fibre optic outdoor cable with central loose tube, up to 24 fibres. For the use in cable ducts and for all applications with low mechanical stress (low tensile force, for example). Non-metallic rodent protection.
Maximum number of fibres 24
Field of application Outdoor
Installation temperature -10 °C - +50 °C
Storage temperature -25 °C - +70 °C
Operating temperature -25 °C - +70 °C
Imprint DATWYLER «cable type» «Datwyler designation» «DIN designation» «no. of fibres» «fibre type» «add. text» «batch no.» «meter marks»
For pulling in or blowing through ducts.
Suitable for laying in cable platforms and cable shafts/trays.
Direct burial.
Tensile performance IEC 60794-1-21 E1
Crush resistance IEC 60794-1-21 E3
Impact IEC 60794-1-21 E4
Repeated bending IEC 60794-1-21 E6
Torsion IEC 60794-1-21 E7
Bend IEC 60794-1-21 E11
Temperature cycling IEC 60794-1-22 F1
Water penetration IEC 60794-1-22 F5
Reaction to fire EN 13501-6
Euroclass Fca
Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2
Armouring (rodent protection) rodent protected
Outer sheath material HDPE