CU 7120 4P / 2x4P F8

Data cable, S/FTP, Category 7A, AWG 23, Euroclass Dca
1200 MHz

1 Inner conductor: AWG23 Bare copper wire
2 PE insulated conductor: 1.5 mm Ø
3 Screen (pair): Alu PETP foil
4 Overall screen: Tinned braided copper
5 Outer sheath: FRNC/LSOH

01_RoHS 04_Propagation 05_Spread 02_PoEp_rt 10_Schielded_EN 06_Density 08_System- 03_LS0H CPR_Dca CPR_Eca

Product variants & stock

Article No. Stock ProductReaction to fireDimensions n x p x [mm (AWG)]Outer sheath dimensions [mm]CU rate [kg/km]Weight [kg/km]Fire load [kWh/m]Packing unitGTIN / EAN
19146600DK
CU 7120 4PDca-s2,d1,a14 x 2 x 0.59 (AWG23)7.632.3600.181000 m drum40393910030532
19146600DL
CU 7120 4PDca-s2,d1,a14 x 2 x 0.59 (AWG23)7.632.3600.18500 m drum40393910030525
19146700DL
CU 7120 2x4PDca-s2,d1,a12 x (4 x 2 x 0.59 (AWG23))7.6 x 16.064.61200.36500 m drum40393910030464

Technical specifications

Electrically and mechanically advanced quality Cat.7<sub>A</sub> data cable - fulfils the requirements of ISO/IEC 11801, IEC 61156-5, EN 50173-1 and EN 50288-9-1. Excellent shielding effect due to individually screened pairs and overall copper braid. Reduced outer diameter. Compatible with all current connecting hardware in accordance with EN 50173 and ISO/IEC 11801.
AWG 23
Tensile strength (4P) 110 N
Tensile strength (2x4P) 220 N
Minimum bending radius during installation 60 mm
Minimum bending radius permanently installed 30 mm
Minimal crush resistance / 10cm 1000 N
Minimum number of impacts 10
Solid / Flex Solid wire
Segregation class d
Category Cat.7A
Loop resistance at 20 °C 134 Ω/km
Operating capacity 44 pF/m
Delay skew 14 ns/100 m
Impedance at 100 MHz, ±5Ω 100 Ω
Transfer impedance 1/10/30 MHz < 5/5/8 mΩ/m
Near end unbalance attenuation LCL at 1-600 MHz 40 dB
NVP % 76
Coupling attenuation 85 dB
GBit/s Up to 10 Gbit/s
Shielding shielded
Data cable for structured premises cabling.
For the transmission of digital and analogue voice, video and data signals.
Suitable for all ICT network applications up to class FA applications (1000 MHz) in accordance with EN 50173-1 and ISO/IEC 11801 and for the transmission of broadband signals (such as cable TV) in accordance with ISO/IEC 11801-4.
Applicable for Power over Ethernet PoE / PoE+ / 4PPoE up to 100W.
Wire colour white/blue, white/orange, white/green, white/brown, according to IEC 60189 and IEC 60708
Field of application Indoor
Installation temperature 0 °C - +50 °C
Operating temperature -20 °C - +60 °C
Imprint DATWYLER «cable type» «additional text» «batch number» «meter marks»
Reaction to fire EN 13501-6
Euroclass Dca
Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA
Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1
Flame spread IEC 60332-3-24, EN 60332-3-24, AREI-RGIE Art.104-F2
Cables standard ISO/IEC 61156-5, EN 50288-9-1
Cat./Class Cat.7A / Class FA
PoE IEEE 802.3bt Type 4 (100W)
Outer sheath material FRNC/LSZH
Outer sheath colour orange

Documentation